Step Closed Loop Autotuning Technique

The Step Closed Loop autotuning technique, which is used by the Step Closed Loop instance of the PID Online Autotuning VI, performs a closed-loop step test. This technique is very accurate and reaches steady state faster than the Step Open Loop technique.

In closed-loop tuning, the PID Online Autotuning VI applies the Step Open Loop response with the controller in a closed loop, and then back-calculates the dynamics of the system by removing the closed loop gain.

The Step Closed Loop autotuning technique measures the deadtime (Td), time constant (T), and process gain (K) values of a controller and multiplies them according to the formulas for the heuristic method in place. For example, most PID VIs use the Ziegler-Nichols method.